Karakteristike
Opis proizvoda
INVT UPS HT1103S 3KVA ,Online,pure sine wave,3KVA/2.7KW, 96VDC,with 8pcs 12V/7AH batteries
HT11 series is online double-conversion UPS with full DSP control technology.
With high input and output power factor
Wide range of input voltage while input PF>99%, Output PF of 0.9ï¼more powerful load capability,
full protection of overvoltage, circuit short and over temperature, LCD/LED display,
monitoring all the operation status, Auto fan speed adjust.
Technical Specs
INPUT
Cold Start YES, default frequency=50Hz or settable
Acceptable Input Voltage 110VAC~288VAC
Phase: Single phase in,single phase out
(200VAC/208VAC/220VAC/230VAC/240VAC)
Line high transfer 288VAC
Line high recovery 281VAC
Input Current
Rating(nominal input voltage) : 14.4A
Input Power Factor â¥0.97
Input Frequency Range 40~70Hz
OUTPUT
Frequency adaptable Settable
Power
Power(kW) max3 : 2.7(2.4 for 200VAC/208VAC)
Output Voltage
Waveform(Bat. Mode) Pure Sine Wave
Nominal voltage 200/208/220/230/240VAC
Voltage regulation ± 1 %
Transient response â¤5% (0% â 100% -0%)
Transient recovery â¤30ms (0% â 100% -0%)
Voltage distortion â¤2% THD, linear load
⤠5% THD, non-linear load
Output Frequency
Synchronization range ±5Hz default
Battery mode (50±0.1) Hz default
Transfer Time
-Line mode to battery mode 0
Efficiency
-Line mode with battery full charged : 88%@100% load, 90%@50% load
-Battery mode: 87%@100% load, 89%@50% load
-Noise(1m away): <45dB@<60%load,60%load
Overload Capability(Inverter) 105%~130%: Transfer to bypass after 1 mins.: 150%:
Transfer to bypass after 30s
Overload Capability(Battery Mode) 105%~130%:shutdown after 10s:
Overload Capability (Bypass Mode) <130%: Long time
>130%&<150%:Shutdown after 10min
>150%&<180%:Shutdown after 5 seconds
BATTERY
Back-up Time: 5.5mins @80% load
Battery-Low Voltage: 88VDC~94VDC depending on load
INDICATOR & ALARM
-Alarm two short one long
-Fault Continuous beeping
INTERFACE
-Smart RS232 Standard Cable support INVT Power Monitor Software
-SNMP(option) Power Managment from SNMP Manager and Web Browser
OPTION
-Intelligent Kits DB9 port, dry contact
-SNMP Kits pluggable type
Charger
-Charging voltage : float:109VDC/boost:112VDC
-Charging current (max) : 1A
-Charging time : 8h recharge to 90%